Panasonic EBL128 Planning Instructions page 41

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
The unit has two programmable relay
Relay output (Re0): NC or NO contacts (set via Win128).
Relay output (Re1): NC or NO contacts (set via Win128).
Connections and examples, see drawings 128-21 & -26. The
unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover's dimensions: (L x W x
H) 129 x 73 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required,
the unit can be mounted in a Waterproof box (IP66 / 67) 3362.
The unit has an LED to indicate communication to the unit or
alarm condition. For more information, see the Product Leaflet.
The technical address is set with an Address setting tool (AST)
3314. The unit has an address label on which the programmed
technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 3361 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 144.
3364
Addressable 2 voltage outputs unit. The unit is connected
directly to the COM loop. External 24 V DC power supply is
required (via a 3366 unit or EBL128).
The unit has two programmable and supervised voltage outputs
(VO0-VO1), intended for alarm devices (e.g. sirens). An end-
of-line capacitor (470nF) is to be mounted in the last device
alt. a capacitor (470nF) in up to five alarm devices:
The unit also has a special voltage output (VO2) intended for
fire door closing only.
closing" and the controlling detectors have to be programmed.
The "fire door closing function" is described on page 80 and
besides that function the output VO2 will also be powerless
approx. 30 sec. after:
- the "/Mains OK input" (terminal 8.) goes high, see below.
- the COM loop communication is interrupted = 3364 has no
connection / communication with EBL128.
The unit also has two inputs, i.e. one for power supply (24 V
DC) and one for "/Mains OK".
VO0: Normally low or high (set via Win128), 24 V DC, 1 A.
VO1: Normally low or high (set via Win128), 24 V DC, 1 A.
VO2: Normally high, 24 V DC, 1 A.
function.)
24 V DC:
From an external power supply (unit 3366 or
EBL128)
/Mains OK: From an external power supply unit (3366) when
45
Relay contacts: max. 2 A @ 30 V DC / 125 V AC.
46
Cont. 1 A, during 10 ms 1.4 A.
EBL128 Planning Instructions V1.1.x
45
outputs:
The trigger condition "Fire door
46
(Fire door closing
39
46
46