Panasonic EBL128 Planning Instructions page 76

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
Example 1
Output:
Control expression:
Explanation:
Example 2
Output:
Control expression:
Explanation:
Example 3
Output:
Control expression:
Explanation:
Example 4
Output:
Control expression:
Explanation:
EBL128 Planning Instructions V1.1.x
Voltage output S0
Pre Warning Zone (10)
Pre-warning activated in zone no. 10 will
activate the output S0.
Relay output R0
General Control disabled AND NOT Door
Open
Controls disabled via menu H2/B7 will
activate the output R0 when the door in
EBL128 is not open (i.e. when it is closed).
Voltage output VO0
Fire Alarm Zone (23) AND Fire Alarm Zone
(24) AND NOT General Fault
Fire alarm activated in zone 23 and zone 24
will activate the output VO0 only if there are
no faults in the system at the same time.
Voltage output S1
Consecutive Fire Alarm (10,10,10,19,1) OR
Consecutive Fire Alarm (10,21,10,40,1)
Fire alarm activated by one of the alarm
points in zone 10 addresses 10-19 or by one
of the alarm points in zone 10 addresses
21-40 will activate the output S1 (i.e. the
alarm point in zone 10 address 20 will not
activate the output S1).
74