Fault: Loss of main power source

The delay time for the fault "Loss of main power source" can be set
via Win128 to 1-300 minutes (default is 30 minutes).
(A delay time >30 minutes is a violation to the EN54-2 standard.)

LCD backlight

In order to reduce the current consumption the LCD backlight will
never be turned on during loss of the main power source.
Exceptions
 Australian convention: The LCD backlight will be turned on
also during loss of the main power source.
 New Zealand convention: The LCD backlight will be turned on
also during loss of the main power source.

Win128 Tools menu

The Win128 "Tools" menu is mostly used when the PC is to be
connected to EBL128 for download / backup etc.
Figure 23 . Win128 "Tools" menu. Some commands might be
disabled since they require the PC/Win128 to be connected and
logged on to EBL128.
Validate..: The SSD can at any be validated, i.e. checked for system
errors, warnings and EN54 violations. (A validation is automatically
done before the download of SSD to EBL128.)
Log on to EBL128: Log on / Log off to EBL128.
Download SSD...: Opens a dialog box for download of SSD to
EBL128 and the "Display Units".
Upload SSD ("Backup")...:
("backup") of SSD from EBL128 and the "Display Units".
118
Log on require the PC to be physically connected to EBL128 and a
password is required.
119
The PC has to be connected and logged on to EBL128.
104
EBL128 Planning Instructions V1.1.x
118
119
Opens a dialog box for upload