Panasonic EBL128 Planning Instructions page 78

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
Figure 15. The Win128 dialog box "Interlocking Combination".
Logical Name:
Displayed in the Win128 Tree and List views.
Default is "Interlocking Combination" that can be changed when
wanted / required.
Area and Point: Each "Interlocking Combination" is presented as
Area-Point (compare with Zone-Address). Area numbers 1-31 are
possible to use and Point numbers 1-63 are possible to use.
Available interlocking outputs list displays all the previous
programmed outputs, Type = "Interlocking Output".
Available interlocking inputs list displays all the previous
programmed inputs with the Triggered by alternative (trigger
condition) 10 = "Interlocking Input".
Select one output and one input in the list respectively.
and the selected output and input will be shown in the Selected
output and Selected input field respectively.
Text = Interlocking text to be shown in the menu H9/C1. Can be
written in this field or in the "Texts" dialog box, see chapter "Creating
the alarm texts via Win128", page 101.
Buzzer checked = activated interlocking input will turn on the
EBL128 buzzer (0.8 / 0.8 sec.)
be automatically turned on again, if a new interlocking input is
activated.
81
Output / Input parent will then show in which unit the output / input
respectively is situated.
82
Priority order: Fire alarm – Pre-warning - Interlocking - Fault.
EBL128 Planning Instructions V1.1.x
82
. The buzzer can be silenced. It will
76
81
Press Select