Configuring with COM 115F
I/O Type 2
S5-115F:
Configuring the I/O Modules
Bits
DI W
2
DI W
4
Digital input
Type number
Num. of I/O Channels : 2
Safety-related
Intermittent
Status:
TYPE INPUT
F1
SEARCH
•
An intermittent signal must be subject to sufficiently frequent status changes detectable by
the CPU. For this purpose, the signal must assume the states "0" and "1" for a period greater
than the PLC cycle time at least once within the second error occurrence time.
•
Signal group ( Vol. 1, 10.17 of the Manual)
•
Discrepancy time ( Vol. 1, 10.6 of the Manual)
Enter "S" here for short and "L" for long discrepancy times.
•
Short and long discrepancy times may be mixed within one word.
1-38
0
1
2
3
4
5
2
2
2
2
2
2
2.0
: 2
DB number
Signal group
: Yes
: Yes
Discrepancy time
F2
F3
F4
COPY
SWAP
DELETE
Figure 1-24. Initialization Form for I/O Type 2
COM 115F / PDC15
6
7
0
1
2
3
2
2
2
2
2
2
(4 to 255):
(0 to 28):
(S/L): S
F5
F6
TYPES
SAVE
S5-115F Manual
4
5
6
7
2
2
2
2
12
3
30 msec.
F7
F8
RETURN
EWA 4NEB 811 6149-02