Blocks
Typical application of the PID control algorithm in the S5-115F
A furnace is to be maintained at a constant temperature by a PID controller.
The temperature setpoint is entered by a potentiometer.
The setpoints and actual values reach the controller via an analog input module. The calculated
manipulated variable is then output via an analog output module. Neither the analog modules
nor the controller itself are safety-related.
The operating mode of the controller is set in input byte 0 (see control word DW 11 in the con-
troller DB).
The controller setting must be calculated for each controlled system by the usual controller design
method.
EB0
+
Channel 0
Channel 1
Setpoint setter
Analog input module
(e.g. 6ES5 460)
Actual value
=
Transducer
The analog signals of the setpoints and actual values are converted into their corresponding
digital values at each sampling instant (determined by time OB 13). From this, OB 251 calculates
the new manipulated variable from which a corresponding analog signal will be generated with
the analog output. This signal is then applied to the controlled system.
6-20
Control byte (DR 11)
W
PID control
algorithm
X
OB 251 with
controller DB
(call in OB 13)
Temperatur sensor
=
Furnace
Figure 6-5. Process Schematic
Manipulated variable
Y
Channel 0
Analog output module
(e.g. 6ES5 470)
Hot gas flow
S5-115F Manual
S5-115F
Controlled
system
Actuator
EWA 4NEB 811 6149-02