STEP 5 Operations
Load Operation:
During loading, information is copied from a memory area, e.g., from the PII, into ACCUM 1.
The previous contents of ACCUM 1 are shifted to ACCUM 2.
The original contents of ACCUM 2 are lost.
Example: Two consecutive bytes (IB 7 and IB 8) are loaded from the PII into the accumulator.
Loading does not change the PII ( Figure 3-2).
Lost
information
Byte d
Byte c
Byte b
Byte a
Loading an input/output value with LPY/LPW operations:
Execution of an LPY/LPW operation triggers the following functions:
Reading of the value.
Exchange of data between the two subunits.
Comparison of the two values of subunits A and B.
If the values are not identical, the response depends on whether the relevant module is
interrupt-generating or not.
- Nonmatching values in the case of noninterrupt-generating DI modules.
To achieve minimum execution time, removal of the discrepancy is not interrogated. The
last valid value is taken as the standard value.
- Nonmatching values in the case of interrupt DI modules
Discrepancy analysis cannot be avoided here because 434 module interrupts are not stored
beyond the access.
Accesses in the AI address area
Accesses in this area are only permissible on the CP 523 implemented in single-channel connec-
tion.
3-12
ACCUM 2
Byte d
Byte c
Byte b
Byte a
0
IB 7
Figure 3-2. Execution of the Load Operation
ACCUM 1
Byte b
Byte a
L IB 7
0
IB 7
L IB 8
0
IB 8
S5-115F Manual
Information
from the PII
IB 7
IB 8
EWA 4NEB 811 6149-02