F2
Copy
You can use this function to transfer the configuration data, one or more I/O words in the
analog area and one or more bytes/bits in the digital area to other addresses. Each entry,
which is checked for validity, must be confirmed with the EXEC key. Any discrepancies are
indicated with an error message in the status line.
The first prompt to appear in the analog range is WORD(S) TO COPY: You can then enter two
numbers, divided with a hyphen, for a word block.
In reply to the prompt "DEST. NO(S):", the system expects the destination address starting
from which the word block or the word is to be stored. The destination end is calculated
internally and displayed in the status line with the message "DEST. END AT WORD xx".
Please note the following rules when entering addresses:
Word numbers may only contain even numbers, i.e. 0, 2, 4 to 254.
The starting address must be smaller than the end address.
The destination address must not lie within the word block to be copied.
When copying word blocks, make sure that there are sufficient addresses available after
the destination address.
Before terminating an input, the cursor can be moved with the cursor control keys and
the space bar can be used for deletion.
If the space bar is used, the routine is aborted.
If there is a feedback address within the address range (source and destination), the
routine will be aborted with the message "FEEDBACK I/O".
If a double assignment of feedback addresses arises due to copying or swapping, this is
indicated in the following ways:
- Type numbers in the type configuration field are displayed in inverse video.
- A "?" is displayed in place of the feedback address.
Example 1
WORD (S) TO COPY : 16-24
DEST. NO(S)
This causes the following transfer to be executed:
Word 16 ---> Word 42
Word 18 ---> Word 44
:
:
Word 24 ---> Word 50
EWA 4NEB 811 6149-02
: 42
Configuring with COM 115F