Siemens SIMATIC S5 Manual page 235

Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Application
Configuring the two-channel digital input modules
Call the configuration form for I/O type 3
Select DI word 0 with the cursor control keys
Enter type no. "3" in the field for bit 0.0 and terminate the input with <Return>
The cursor jumps to the configuration field.
Enter the following in the configuration field
DB number
(4 to 255):
Signal group
Interrupt generating (Y/N) : N
Inp. volt.
Discrepancy time
CH DQ Channel No.
CH DQ Byte addr. (0 to 125):
Repeat the entries for addresses...
(You can copy the configuration data of bits 0.0 also to addresses 0.1 to 3.7
( 1.2.2)).
Figure 7-6 shows the finished entries.
I/O type 3
S5-115F:
Configuring the I/O Modules
Bits
DI-W
0
DI-W
2
Digital input
Type number
Num. of I/O Channels
Safety rel.
Intermittent
Feedback module required :
Check DQ 1/2 Channel
Status:
TYPE INPUT
F1
SEARCH
Save your configuration data on the default program file by pressing F6
Terminate the input by pressing F8
7-8
13
(0 to 28):
0
(24/220):
24
V
(S/L): S
30
msec
(1/2):
1
0 SUBUNIT:A
0
1
2
3
4
5
3
3
3
3
3
3
2.0
: 3
DB number
: 2
Signal group
: Yes
Interr. genrating
: No
Inp. volt.
Discrepancy
CH DQ Channel No.
CH DQ Byte addr. (0 to 125):
F2
F3
F4
COPY
SWAP
DELETE
Figure 7-6. Initialization Screen Form for I/O Type 3
COM 115F / PDC15
6
7
0
1
2
3
3
3
3
3
3
3
(4 to 255):
(0 to 28):
(Y/N): N
(24/220):
(S/L): s
(1/2):
F5
F6
TYPES
SAVE
S5-115F Manual
4
5
6
7
3
3
3
3
13
0
24
V
30
msec
1
0
SUBUNIT:A
F7
F8
RETURN
EWA 4NEB 811 6149-02

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5-115f

Table of Contents