S5-115F Manual
Error
Con-
Error Message Text
Identi-
sec.
fier
No.
Progr.
105
01
Configured scan time
exceeded
Additional info. 1:
Configured scan time/
10 msec.
Additional info. 2:
Actual scan time/10 msec.
105
02
OB 13 call could not be
processed:
CPU error
105
03
Configured test scan time
cannot be maintained
EWA 4NEB 811 6149-02
Possible Cause
Error group No. 21
-
Endless loop in user program
-
Configured scan time too short
Desired scan time, decimal display
Actual scan time, decimal display
Error group No. 01
-
FIOBT REQ signal has not been
deleted:
-
CPU HW defective
-
Interrupt disabled too long
-
115F operating system in error
Error group No. 01
- Endless loop in restart OB
- Configured test scan time too short
PLC Error Messages
Remedy
-
Remove program errors
-
Increase configured scan time
( Vol. 1, 10.3.2 of the
Manual)
CAUTION:
Value requires authorization
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Replace CPU
-
Check distribution of
interrupt disable operations
in user program
-
Service
Warm restart:
1. POWER OFF/ON
2. Stop/Run
-
Remove program errors
-
Remove program errors
Caution:
Value requires authorization
Warm restart:
1. POWER OFF/ON
2. Stop/Run
B-63