Upgrading to COM ET 200 Windows or to IM 308-C

13.3 The upgrading procedure

Precondition
Procedure
13-8
COM ET 200 Windows provides support for upgrading from an IM 308-B to
an IM 308-C.
You are operating a system with an IM 308-B configured with COM ET 200
(up to V 4.x).
To upgrade an existing system to an IM 308-C, proceed as follows:
1. Load the program file generated with COM ET 200 (V 4.x) into the PG or
PC.
If the original program file is no longer available, you must first load the
contents of the E(E)PROM with an earlier version of COM ET 200.
2. Load all the type files that you required for the old program file into the
directory "\KONVER4X".
3. In COM ET 200 Windows, use File
you want to convert and press the "OK" button to confirm.
Result: A window detailing the original format of the program file
appears on the screen.
4. Confirm your choice by answering "OK" at the prompt.
Result: COM ET 200 Windows converts the program file into a new
format.
5. Save the converted program file under a new name.
6. If you want to expand or modify the configuration, you must observe the
notes in Section 13.2.
If you do not want to modify the configuration, export the data to a
memory card with File
7. Insert the memory card in the IM 308-C.
8. Remove the IM 308-B and install the IM 308-C.
Open to select the program file
Export
Memory card.
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a