Parameterizing, saving and documenting the configuration with COM ET 200 Windows
8.4.2

Save to 32 K EEPROM (in S5-95U)

32 K EEPROM for
S5-95U
Precondition
Saving
configuration data
to 32 K EEPROM
8-26
If you have the S5-95U as DP master, you use a special memory module, an
EEPROM with a capacity of 32 Kbytes, supplied with the S5-95U with DP
master interface.
In case you have to re-order the 32 K EEPROM, you will find the order num-
ber in Appendix F.
You have installed the 32 K EEPROM in the S5-95U as described in Section
4.5.
Note
The configuration data of a master system cannot be saved by inserting the
32 K EEPROM in the EEPROM slot of the PG or an external programming
unit.
You can save the configuration data of a master system in the S5-95U only
when the 32 K EEPROM is inserted in the S5-95U.
The procedure for saving the configuration data to the 32 K EEPROM is as
follows:
1. In COM ET 200 Windows, select File
2. Enter the current baud rate of the DP master
(Default after reset = 19.2 kbaud).
The current baud rate is available in EB 63 (value 05
Table 8-8
Contents of EB 63 (baud rate)
EB 63
00
H
01
H
02
H
03
H
04
H
06
H
Export
DP master.
is not used):
H
Baud rate
9.6 kbaud
19.2 kbaud
93.75 kbaud
187.5 kbaud
500 kbaud
1500 kbaud
ET 200 Distributed I/O System