F211
RR Speed Reference Setpoint #1 (frequency)
Program
Frequency Setting Parameters
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control
mode.
See
F210
for further information on this setting.
This parameter sets the RR Speed Reference Setpoint #1 (frequency) and is
the frequency that is associated with the setting of F210.
RR Speed Reference Setpoint #2 (%)
Program
Frequency Setting Parameters
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
See
F210
for further information on this setting.
This parameter sets the RR input level that represents RR Reference Setpoint
#2 (frequency) (torque or frequency). This value is entered as 0 – 100% of the
0 – 10 VDC RR input signal range.
RR Speed Reference Setpoint #2 (frequency)
Program
Frequency Setting Parameters
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control
mode.
See
F210
for further information on this setting.
This parameter sets RR Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F212.
RR Torque Reference Setpoint #1 (%)
Program
Torque Setting Parameters
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Torque Control
mode.
This is accomplished by establishing an associated V/f output pattern for a given
RR input level and motor load.
See
F210
for further information on this setting.
This parameter sets RR Torque Reference Setpoint #1 and is the output torque
value that is associated with setting of F210. This value is entered as 0 – 250%
of the rated torque.
H7 ASD Operation Manual
Speed Reference
Speed Reference
Speed Reference
Setpoints
RR
Direct Access Number — F211
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Hz
Direct Access Number — F212
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F213
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Hz
Direct Access Number — F214
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
F214
89