Toshiba H7 Operation Manuals page 166

Adjustable speed drive
Hide thumbs Also See for H7:
Table of Contents

Advertisement

F622
Abnormal Speed Detection Filter Time
Program
Protection Parameters
This parameter sets the time that an overspeed condition must exist to cause a
trip.
Overspeed Detection Frequency Range
Program
Protection Parameters
This parameter sets the upper level of the Base Frequency range that, once
exceeded, will cause an Overspeed Detected alert.
Speed Drop Detection Frequency Range
Program
Protection Parameters
This parameter sets the lower level of the Base Frequency range that, once
exceeded, will cause a Speed Drop Detected alert.
Overvoltage Stall Level (fast)
Program
Protection Parameters
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Overvoltage Stall. An Overvoltage Stall increases the output
frequency of the drive during deceleration for a specified time in an attempt to
prevent an Overvoltage Trip.
If the overvoltage condition persists for over 250 µS, an Overvoltage Trip will
be incurred.
Note: This feature may increase deceleration times.
H7 ASD Operation Manual
Abnormal Speed Settings
Abnormal Speed Settings
Abnormal Speed Settings
Stall
Direct Access Number — F622
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — No
Minimum — 0.01
Maximum — 100.0
Units — Seconds
Direct Access Number — F623
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Direct Access Number — F624
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Direct Access Number — F625
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 50.00
Maximum — 250.0
Units — %
F625
159