F221
RX Torque Reference Setpoint #2 (%)
Program
Torque Setting Parameters
⇒
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given RX input level and motor load.
See
F220
for further information on this setting.
This parameter sets RX Torque Reference Setpoint #2 (%) and is the output
torque value that is associated with setting of F218. This value is entered as
-250 to +250% of the rated torque.
H7 ASD Operation Manual
Setpoints
RX
⇒
⇒
Direct Access Number — F221
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
F221
93