Using a shielding bus
If a shielding bus is used, proceed as follows:
1. Attach the cable shield to a grounded shielding bus after the cable entry point in the cabinet.
To do this, expose the cable shield of the cable.
2. Continue routing the shielded cable as far as the module, but do not make a connection to
the shield there.
Using the shield connection on the D4x5‑2/CX32-2
1. Unscrew the holding clamp of the shield connection at the top of the D4x5‑2/CX32‑2 until
there is a space below the clamp (M3 screw, Torx T10).
2. Insert the cable. To do this, expose the cable shield first.
3. Tighten the fixing bracket so that the cable shield and cable are pressed against the shield
connection (tightening torque 0.8 Nm).
This figure shows where to attach the cables to the front panel connector and where to apply
the cable interference suppression using the shield connecting element.
Figure 4-8
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
Shield connection using the D4x5-2 DP/PN as an example