Commissioning (software)
7.18 Deleting data
Memory reset with the mode switch
You can perform a memory reset with the mode switch when you are offline with the
SIMOTION D4x5‑2.
NOTICE
Damage from electrostatic discharge
The rotary switch can be destroyed by static electricity.
Operate the rotary switch only with an insulated screwdriver.
Comply with the ESD rules.
Proceed as follows to reset the memory:
1. Place the mode switch in the STOP position (switch setting 2, see figure below).
Figure 7-72
2. When the STOP LED is steadily yellow, turn the switch to the MRES position (switch
position 3). The STOP LED starts to flash slowly (slow yellow flashing).
Wait until the STOP LED stops flashing.
3. Turn the selector back to the STOP setting.
4. You must turn the selector back to the MRES position again within 3 seconds. The memory
reset will now be performed.
The SIMOTION D4x5‑2 has completed the memory reset when the STOP LED is steadily
yellow.
Note
If you do not return the mode switch to the MRES position (switch position 3) within 3
seconds, but take longer, then the memory reset may not be performed. You must then
repeat the procedure.
5. Now move the mode switch back to the required operating mode.
314
Memory reset with the mode switch (position 2 = STOP)
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B