LED
Color
DP
–
(PROFIdrive
cyclic opera‐
tion)
Green
Red
RDY and
Red
DP
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
State
Off
Cyclic communication has not (yet) taken place.
Note:
The PROFIdrive is ready to communicate when
the CX32‑2 is ready for operation (see RDY LED).
Continuous
Cyclic communication is taking place.
light
Flashing
Full cyclic communication has not yet taken place.
0.5 Hz
Possible causes:
● D4x5‑2 does not transfer any setpoints.
● During isochronous operation, no global
control (GC) or a faulty global control (GC) is
transferred by the controller.
Flashing
D4x5‑2 sends faulty parameterization/configura‐
0.5 Hz
tion.
Flashing
Cyclic bus communication has been interrupted or
2 Hz
could not be established.
Flashing
Bus error - communication has been interrupted.
2 Hz
Description, cause
Diagnostics
9.1 Diagnostics via LED displays
Remedy
–
–
–
Adapt configuration between
D4x5‑2 and CX32‑2
Correct fault
Correct fault
395