Connection Cross-Sections, Cable Lengths - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Electrical installation
4.8 Power connections
4.8.2

Connection cross-sections, cable lengths

Connection cross-sections
The connection cross-sections for the line connection, motor connection, and ground
connection for your device are specified in the tables provided in the "Technical
specifications" section.
Cable lengths
The maximum permissible cable lengths are specified for standard cable types or cable
types recommended by SIEMENS. Longer cables can only be used after consultation.
The listed cable length represents the actual distance between the converter and the motor,
taking account factors such as parallel laying, current-carrying capacity, and the laying
factor.
● Unshielded cable (e.g. Protodur NYY): max. 450 m
● Shielded cable (e.g., Protodur NYCWY, Protoflex EMV 3 Plus): max. 300 m.
Note
The cable lengths specified are also valid if a motor choke is in use (option L08).
Note
The PROTOFLEX-EMV-3 PLUS shielded cable recommended by Siemens is the protective
conductor and comprises three symmetrically-arranged protective conductors. The individual
protective conductors must each be provided with cable eyes and be connected to ground.
The cable also has a concentric flexible braided copper shield. To comply with EN 61800-3
regarding radio interference suppression, the shield must be grounded at both ends with the
greatest possible surface area.
On the motor side, cable glands that contact the shield with the greatest possible surface
area are recommended for the terminal boxes.
80
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A