Table of Contents

Advertisement

4. For both nodes p0009 = 0, carry out "Copy RAM to ROM" followed by a POWER ON.
5. Set all CBE20 to the isochronous mode by setting p8812[0] = 1.
6. Limit the maximum number of nodes with p8811 = 16.
7. For both nodes p0009 = 0, carry out a "Copy RAM to ROM" followed by a POWER ON in
8. Define the send data for node 1
9. Define the receive data for node 2
10. Define the send data for node 2
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
order to activate the modified firmware versions and the new settings in the CBE20.
– Define the PZD that node 1 should send:
p2051[0] = drive1:r0898 (PZD length is 1 word)
p2061[1] = drive1:r0079 (PZD length is 2 words)
p2061[3] = drive1:r0021 (PZD length is 2 words)
– Place this PZD into the send buffer (p8871) of node 1:
p8871[0] = 1 (r0898)
p8871[1] = 2 (r0079 first part)
p8871[2] = 3 (r0079 second part)
p8871[3] = 4 (r0021 first part)
p8871[4] = 5 (r0021 second part)
This means that you have defined the position of the data in the 16-word telegram of
node 1.
– Specify that the data placed in the receive buffer p8872 of node 2 in locations 0 to 4 is
received from node 1:
p8872[0] = 1
p8872[1] = 1
p8872[2] = 1
p8872[3] = 1
p8872[4] = 1
– Define that PZD1, PZD2 and PZD3 of node 1 are saved in the receive buffer p8870 of
node 2 in locations 0 to 4:
p8870[0] = 1 (PZD1)
p8870[1] = 2 (PZD2 first part)
p8870[2] = 3 (PZD2 second part)
p8870[3] = 4 (PZD3 first part)
p8870[4] = 5 (PZD3 second part)
– r2050 [0], r2060 [1] and r2060[3] now contain the values of PZD 1, PZD 2 and PZD 3
of node 1.
– Specify the PZD that node 2 should send:
:p2051[0] = drive1:r0899 (PZD length is 1 word)
– Place this PZD in the send buffer (p8871) of node 2:
p8871[0] = 1
6.10 Communication via SINAMICS Link
Operation
359