Electrical installation
4.11 Other connections
4.11.4

Main Contactor (Option L13)

Description
The cabinet unit is designed as standard without a line contactor. Option L13 (main
contactor) is needed if a switching element is required for disconnecting the cabinet from the
supply (necessary with EMERGENCY OFF). The contactor is energized and supplied within
the cabinet.
Connection
Table 4- 36
Terminal
NO: normally-open contact, NC: normally-closed contact, COM: mid-position contact
1)
Max. connectable cross-section: 4 mm²
4.11.5

Sinusoidal Filter (Option L15)

Description
The sine-wave filter limits the voltage gradient and the capacitive charge/discharge currents
which usually occur with inverter operation. It also prevents additional noise caused by the
pulse frequency. The service life of the motor is as long as that attained with direct mains
operation.
CAUTION
If a sine-wave filter is connected to the converter, the converter must be activated during
commissioning to prevent the filter from being destroyed (see "Commissioning").
CAUTION
When using a sine-wave filter, the drive must not be operated without a connected motor as
otherwise the filter could be destroyed.
126
Terminal block X50 – checkback contact "main contactor closed"
Designation
1)
4
NO
5
NC
6
COM
Technical specifications
Max. load current: 10 A
Max. switching voltage: 250 V AC
Max. switching capacity: 250 VA
Required minimum load: ≥1 mA
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A