Hitachi PC-ARF Technical Catalogue page 459

Table of Contents

Advertisement

6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)
Export buttons
Save to file button writes in a selected comma-separated values file the content of the table.
Copy to clipboard button will set in your clipboard the content of the table, separating the information by tabs.
In both cases the information of the table is ready to create an easy view of the information and an easier exportation to
other programs like Excel.
Available data for Packaged
The available data for CSNET WEB for Packaged is:
Address
Name
(Note 1)
0
EXIST
1
SYSTEM_ADDRESS
2
UNIT_ADDRESS
3
SET_ONOFF
4
SET_MODE
5
SET_FAN
6
SET_TSET
7
SET_LOUVER
8
SET_CENTRAL
9
READ_ONOFF
10
READ_MODE
11
READ_FAN
12
READ_TSET
13
READ_LOUVER
14
RCS_GROUP
15
TIN
16
TOUT
17
TGAS
443
443
TCGB0106 rev.0 - 12/2014
Description
0: Not exist
1: Exist
H-LINK 1: 0~15
H-LINK 2: 0~63
ON/OFF setting order:
0: Stop
1: Run
Mode setting order:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Fan setting order:
0: Low
1: Medium
2: High
Setting temperature
17ºC ~ 30ºC
Louver setting
0 ~ 7 (7 is Auto)
Central Setting:
Bit 0: ON/OFF (always can be stopped)
Bit 1: Mode
Bit 2: Setting temperature
Bit 3: Fan
ON/OFF read:
0: OFF
1: ON
Mode read:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Fan read
0: Low
1: Medium
2: High
Setting temperature read
(17ºC to 30ºC)
Louver read
0 ~ 7 (7 is Auto)
Remote controller group
0 ~ 255
Inlet temperature (Note 2)
Outlet temperature (Note 2)
Gas pipe temperature (Note 2)
Read/Write
Read
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
6

Advertisement

Table of Contents
loading

Table of Contents