4 Individual remote controls
PC-ART
Step
No.
15
Abnormal operation occurrence counter
16
Indoor unit instantaneous power failure occurrence counter.
17
Remote control to indoor unit transmission error occurrence counter.
18
Abnormal inverter operation occurrence counter.
- Counts up to 99.
- For counts above "99", it will always read "99".
N O T E
If a transmission error lasts for more than 3 minutes, one occurrence is added to the counter.
Stored data can be deleted by following the instructions given in section "PCB self-checking procedure using the remote control".
Step
No.
19
Swing louver sensor.
- 00 : Normal
- FF : Abnormal.
Step
No.
20
Discharge pressure (high) (x 0.1 MPa).
21
Suction pressure (low) (x 0.01 MPa).
Control information:
22
Indicates internal remote control information. It has no specific meaning.
Operating frequency (Hz):
23
The total frequency is indicated when several compressors are running at once.
151
TCGB0106 rev.0 - 12/2014
Abnormal operation occurrence counter
Indication of automatic swing louver status
Compressor pressure/frequency indicator
E1
01
E2
00
E3
00
E4
00
4
F1
00
H1
18
H2
04
H3
44
H4
44