5 Centralised remote controls
PSC-A64S
Setting for Each Group
a. Depress the "ZONE" switch and select the zone to set.
b. Depress the "GROUP"  switch to select the group to set. Then, the Ref. Nº and I.U. Add. of the indoor unit
set as the master unit of selected group are indicated.
[Group Selection]
Depress the "GROUP"  switch, and the flickering indication of group Nº is changed in order as shown below.
*
Only the group Nº to set is indicated.
5 Setting Procedure
Depress the "RUN/STOP" switch and the selected group is set with demand control, and the "" and "DEMAND" indica-
tions appear.
In the case where there is one or more group with demand setting in the zone, the "" indication of zone turns ON.
(Every time the "RUN/STOP" switch is depressed, the demand control is set and canceled alternately.)

5.3.4.4 Option setting


Changing to Option Setting Mode
1 Depress the "CHECK" switch for more than 3 seconds while all the groups are stopped. The central station is
changed to the option setting mode and the "CHECK" indication appears, and "1" (Master Unit Setting Mode) is indi-
cated on the 7-segment for check.
AT T E N T I O N
When there is a group in operation, the central station can not be changed to the check mode.
2 Depress the "CHECK" switch and change the indication of the 7-segment.
3 Depress the "RESET" switch and the central station is changed to the normal mode.
391
TCGB0106 rev.0 - 12/2014
"" and "SET" Indications: ON
(The demand control is set.)
7-Segment
A
Fixing Operation Mode
b
Fixing Setting Temperature
c
Fixing Cooling Only
d
Fixing Air Flow
E
Auto COOL / HEAT
All
flickering
Function