Access Modular Controller 2
For RS-485 four wire connection, set the AMC-MUX DIL switch at positions 3, 5 and 6 to ON.
On the upper side of the AMC panel, put the jumper on the two pins on the right hand side of
the connector 8. Also refer to . Set the RS-485 address of the AMC2 controller using the DIL
switch. Refer to DIL switch selector, page 61. A complete connection diagram of the RS-485
host interface is shown in .
Notice!
See the notices for setting the RS-232 / RS-485 converter.
Notice!
If a four-wire connection is used the interface must be set up as a crosslink.
Bosch Access Systems V.B.
Installation manual
Installing | en
59
2020-01 | V02 |