en | Installing
The following conditions apply for an RS-485 bus system:
To use RS-485 mode at the AMC2-4R4 , connect the data cables to the pluggable screw
connector of the RS-485 host interface. The setting of the AMC2-4R4 must correspond with
the settings of the RS-232 / RS-485 converter.
Figure 4.34: RS-485 host interface
Figure 4.35: RS-485 host interface
Figure 4.36: RS-485 host interface
2020-01 | V02 |
A bus system consists of a bus line and/or one or more branch lines.
Cable lengths exceeding 100 m (300 ft) must be installed as bus lines.
Branch lines are branching connections from a bus line.
Peripheral devices are AMC2 which are connected to the host computer.
Maximum cable length of a bus line must not exceed 1200 m (4000ft).
The cable length of branch lines must not exceed 100m (330ft).
Any bus line conductor connects up to eight AMC2. Do not exceed the maximum number
of devices.
Installation manual