Table 276: CMSUM Output signals
Name
I3P
IRES
3.20.20

Transformer data combiner OLGAPC

3.20.20.1
Identification
Function description
Transformer data combiner
3.20.20.2
Function block
Figure 160: Function block
3.20.20.3
Functionality
The transformer data combiner function OLGAPC is intended for the voltage
regulator function OL5ATCC.
3.20.20.4
Operation principle
The function of OLGAPC is to collect data from a parallel transformer via GOOSE
communication. The TR_DAT output, which contains the combined input data, is
connected to the OL5ATCC function block.
3.20.20.5
Application
See the application example in
REX640
Technical Manual
Type
Description
SIGNAL
Summed three-phase currents
SIGNAL
Calculated residual current of summed three-
phase currents
IEC 61850
identification
OLGAPC
Figure 161
.
Basic functions
IEC 60617
ANSI/IEEE C37.2
identification
device number
OLGAPC
OLGAPC
285