Modbus Settings - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Parameter
Values (Range)
1=On
MMS
0=Off
1=On
3.1.17

MODBUS Settings

Table 23: Non group settings
Parameter
Values (Range)
Operation
1=on
5=off
Port
1=COM 1
2=COM 2
3=Ethernet - TCP 1
Mapping selection
1...2
Address
1...254
Link mode
1=RTU
2=ASCII
TCP port
1...65535
Parity
0=none
1=odd
2=even
Start delay
0...20
End delay
0...20
CRC order
0=Hi-Lo
1=Lo-Hi
Client IP
Write authority
0=Read only
1=Disable 0x write
2=Full access
Time format
0=UTC
1=Local
Table continues on the next page
68
Unit
Step
Unit
Step
1
1
1
1
1
1MRS759142 F
Default
Description
1=On
MMS communica-
tion mode
Default
Description
5=off
Enable or disable
this protocol in-
stance
3=Ethernet - TCP 1
Port selection for
this protocol in-
stance. Select be-
tween serial and
Ethernet based
communication.
1
Chooses which
mapping scheme
will be used for this
protocol instance.
1
Unit address
1=RTU
Selects between
ASCII and RTU
mode. For TCP, this
should always be
RTU.
502
Defines the listen-
ing port for the
Modbus TCP server.
Default = 502.
2=even
Parity for the serial
connection.
4
Start delay in char-
acter times for seri-
al connection
4
End delay in charac-
ter times for serial
connections
0=Hi-Lo
Selects between
normal or swap-
ped byte order for
checksum for seri-
al connection. De-
fault: Hi-Lo.
0.0.0.0
Sets the IP address
of the client. If set
to zero, connection
from any client is
accepted.
2=Full access
Selects the control
authority scheme
1=Local
Selects between
UTC and local time
for events and
timestamps.
Technical Manual
REX640