ABB RELION REX640 Technical Manual page 967

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
blocked when the ratio between residual current of the parallel line and protected
lines exceeds the
Figure 539: Operation principle of parallel line compensation functionality
The operation time delay is defined with the
The timer can be disabled with the
blocks the OPERATE_Zx (x = 1...5) output of the phase-to-earth measuring elements.
Phase-to-phase impedance measuring elements
The phase-to-phase distance protection is suitable as a basic protection function
against two-phase short circuit faults in various networks, regardless of the
treatment of the neutral point. The short circuit fault protection is enabled with
the
The reach of the phase-to-phase measuring elements is based on the loop
impedance
REX640
Technical Manual
Fact EF current Bal configuration setting.
The parallel line compensation functionality is only used with single
phase-to-earth faults. Parallel line compensation is not used if multiple
phases are included into fault (more than one single earth fault releases).
d
l
IN2
IN1
Z<
Parallel lines are mutually coupled
Op Mod PP loops Znx (x = 1...5) = "True" setting.
X
Gnd operate Dl Znx (x = 1...5) setting.
Gnd Op Dl mode Znx = "False" setting. This
Protection functions
R
(Equation 268)
967