ABB RELION REX640 Technical Manual page 692

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Figure 393: Setting range for biased low stage
If the biasing current is small compared to the differential current of the phase
angle between the winding 1 and winding 2 phase currents is close to zero (in
a normal situation, the phase difference is 180 degrees), a fault has most likely
occurred in the area protected by TR2PTDF. Then the internal blocking signals of the
biased stage are inhibited.
Instantaneous high stage
The instantaneous high stage operation can be enabled and disabled with the
Enable high set setting. The corresponding parameter values are "TRUE" and
"FALSE."
The operation of the instantaneous high stage is not biased. The instantaneous
stage operates and the output OPR_HS is activated when the amplitude of the
fundamental frequency component of the differential current exceeds the set
operate value or when the instantaneous value of the differential current exceeds
2.5 times the value of
maximum asymmetric short circuit current.
If the biasing current is small compared to the differential current or the phase
angle between the winding 1 and winding 2 phase currents is close to zero (in a
normal situation, the phase difference is 180 degrees), a fault has occurred in the
area protected by TR2PTDF. Then the operation value set for the instantaneous
stage is automatically halved and the internal blocking signals of the biased stage
are inhibited.
692
High operate value . The factor 2.5 (=1.8 × √2) is due to the
1MRS759142 F
High
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents