Basic functions
The actual state is reflected on the CONTROL function outputs. Only one output is
active at a time.
Table 70: Truth table for CONTROL
CTRL_OFF
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
3.8.3

L/R control access

Four different Local/Remote control access scenarios are possible depending on the
selected station authority level: "L,R", "L,R,L+R", "L,S,R" and "L, S, S+R, L+S, L+S+R". If
control commands need to be allowed from multiple levels, multilevel access can be
used. Multilevel access is possible only by using the station authority levels "L,R,L+R"
and "L, S, S+R, L+S, L+S+R". Multilevel access status is available from IEC 61850 data
object CTRL.LLN0.MltLev.
Control access selection is made with R/L button or CONTROL function block
and IEC 61850 data object CTRL.LLN0.LocSta. When writing CTRL.LLN0.LocSta IEC
61850 data object, IEC 61850 command originator category station must be used by
the client, and remote IEC 61850 control access must be allowed by the relay station
authority. CTRL.LLN0.LocSta data object value is retained in the nonvolatile memory.
The present control status can be monitored in the HMI or PCM600 via Monitoring >
Control command with the
CTRL.LLN0. LocKeyHMI.
IEC 61850 command originator category is always set by the IEC 61850 client.
The relay supports station and remote IEC 61850 command originator categories,
depending on the selected station authority level.
3.8.4

Station authority level "L,R"

Relay default station authority level is "L,R". In this scenario only local or remote
control access is allowed. Control access with IEC61850 command originator
category station is interpreted as remote access. There is no multilevel access
136
Input
CTRL_LOC
CTRL_STA
N/A
N/A
TRUE
N/A
FALSE
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
LR state parameter or from the IEC 61850 data object
CTRL_REM
CTRL_ALL
N/A
N/A
N/A
N/A
N/A
N/A
TRUE
TRUE
FALSE
TRUE
FALSE
FALSE
1MRS759142 F
Output
OFF = TRUE
LOCAL =
TRUE
STATION =
TRUE
REMOTE =
TRUE
ALL = TRUE
OFF = TRUE