Protection functions
Table 808: ROVPTOV Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 809: ROVPTOV Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.5.3.9
ROVPTOV Monitored data
Table 810: ROVPTOV Monitored data
Name
Type
START_DUR
FLOAT32
ROVPTOV
Enum
4.5.3.10
Technical data
Table 811: ROVPTOV Technical data
Characteristic
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite
time mode
Suppression of harmonics
1
Residual voltage before fault = 0.0 × U
ted from random phase angle, results based on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
870
Unit
Unit
ms
Values (Range)
0.00...100.00
1=on
2=blocked
3=test
4=test/blocked
5=off
1, 2
U
= 2 × set
Fault
Start value
, f
= 50 Hz, residual voltage with nominal frequency injec-
n
n
Step
Default
1=on
Step
Default
1
20
Unit
%
Value
Depending on the frequency of the measured voltage:
f
±2 Hz
n
±1.5% of the set value or ±0.002 × U
Minimum
Typical
48 ms
51 ms
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
1MRS759142 F
Description
Operation Off / On
Description
Reset delay time
Description
Ratio of start time / op-
erate time
Status
n
Maximum
54 ms
REX640
Technical Manual