Mounting - Bosch Rexroth IndraControl VAU 01.1U Project Planning Manual

Vau 01.1u ups with usb interface
Hide thumbs Also See for Rexroth IndraControl VAU 01.1U:
Table of Contents

Advertisement

26/63
Bosch Rexroth AG
Dimensions, Mounting and Dismounting
5.3.2

Mounting

Mounting the UPS on the mount‐
ing rail
Attaching the end clamps
The LED displays must not be covered.
Provide the following minimum distances for installation and sufficient
cooling:
To the bottom side 50 mm
To the top side 80 mm
Lay all connecting cables in loops.
Use strain reliefs for the cables.
Keep as much distance as possible to noise sources, when installing the
VAU 01.1U.
Only mounting rails TH 35-7.5 and TH 35-15 made of steel ac‐
cording to EN 60715 are permitted.
Determine the distance of the mounting holes according to EN 60715 appen‐
dix B.
Hang the UPS onto the mounting rail from above. Then exert slight pressure
to engage the UPS in the lower section of the housing.
Mount end clamps on the mounting rail on both sides of the VAU 01.1U to
avoid lateral moving of the UPS if vibrations occur. The end clamps are avail‐
able as accessories, see
chapter 9.2 "Accessories" on page
1
End clamps on the mounting rail
Fig.5-3:
End clamps
DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
54.
1