Ul And Csa Certified; Wear Parts; Compatibility Test - Bosch Rexroth IndraControl VAU 01.1U Project Planning Manual

Vau 01.1u ups with usb interface
Hide thumbs Also See for Rexroth IndraControl VAU 01.1U:
Table of Contents

Advertisement

24/63
Bosch Rexroth AG
Technical Data
4.4.3

UL and CSA certified

4.5

Wear Parts

4.6

Compatibility Test

The standard EN 60204-1 (safety of machinery, general requirements on the
electrical equipment of the machines) can be used for the electrical equip‐
ment of the machines.
NOTICE
The CE marking is only valid for the device in its delivery status (ex works).
After modifying the device, the CE conformity has to be verified.
The devices of the VAU 01.1U product family are certificated according to
UL508 (Industrial Control Equipment) and
C22.2 no. 142-M1987 (CSA)
UL file no. E210730
However, there can be combinations or stages of expansions with limited or
missing certification. Therefore verify the certification by using the UL label on
the device.
To guarantee an UL- and CSA-compliant operation, the following
conditions have to be fulfilled:
Use only insulated copper wire suitable for at least 60/75 °C.
NOTICE
The UL- and CSA- marking is only valid for the device in its delivery status.
After having modified the device the UL and CSA compliance must be veri‐
fied.
The service life of the battery is approximately ten years at +25 °C. The serv‐
ice life is halved with each 10 °C temperature rise. For storing the VAU
01.1U, please do observe
51.
All Rexroth controls and drives are developed and tested according to the lat‐
est state-of-the-art of technology.
As it is not possible to follow the continuing development of all materials (e. g.
lubricants in machine tools) which may interact with our controls and drives, it
cannot be completely ruled out that any reactions with the materials used by
Bosch Rexroth might occur.
For this reason, before using the respective material a compatibility test has
to be carried out for new materials (e. g. lubricants and cleaning agents) and
our housing or our housing materials.
DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
Loss of CE conformity due to modifications of
the device.
Loss of UL and CSA compliance due to
changes on the device.
chapter 8.4 "Storing the VAU 01.1U" on page