DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
Switching off the UPS after a
switch-on duration < 120 seconds
for switch positions 4 to 7
Activation of the supply voltage
during UPS operation
"not" signaled to the connected PC. Firstly, after this time delay has expired,
UPS operation is signaled to the connected PC. As soon as the UPS time "t "
has expired, the output voltage on the VAU 01.1U is switched off.
Switch position S1
0
1
2
3
Fig.6-9:
Switch position S1
24V In
UPS operation
24V Out
5 seconds
24V In
Input voltage DC 24 V on the UPS of the power supply unit.
UPS opera‐
Signal to the connected PC that the UPS is in the buffer mode and
tion
that the supply voltage "24V Out" switches off after a set time.
24V Out
Output voltage DC 24 V of the UPS to supply the connected PC.
Fig.6-10:
Timing
If the input voltage on the UPS VAU 01.1U drops, the output voltage is buf‐
fered via the battery and signaled to the connected PC. After the UPS time "t"
has expired, the output voltage on the VAU 01.1U is switched off.
Switch position S1
4
5
6
7
Fig.6-11:
Switch position S1
24V In
UPS operation
24V Out
> 120 seconds
5 seconds
24V In
Input voltage DC 24 V on the UPS of the power supply unit.
UPS opera‐
Signal to the connected PC that the UPS is in the buffer mode and
tion
that the supply voltage "24V Out" switches off after a set time.
24V Out
Output voltage DC 24 V of the UPS to supply the connected PC.
Fig.6-12:
Timing
If after initiated UPS operation, the supply voltage is switched on again, the
UPS operation is not interrupted. In this case, after the set UPS time has ex‐
pired the UPS output voltage of the VAU 01.1U ("24V Out") is switched off
and is switched on again after approx. 6 seconds.
Bosch Rexroth AG
Operating and Display Components
UPS time "t"
5 seconds
60 seconds
120 seconds
180 seconds
t
UPS time "t"
5 seconds
60 seconds
120 seconds
180 seconds
6 seconds
t
35/63