IndraControl VAU 02.1 Uninterruptible
Power Supply
Fig. 9-3: Serial interface XF50
Pin name
Rx
Tx
GND
Tab. 9-3: Pin assignment XF50
10 Mounting, demounting and electric installation
10.1 Housing dimensions
UPS
VAU 02.1S
Tab. 10-1: Dimensions
10.2 Installation notes
The UPS is intended for front upright mounting
●
The LED displays may not be hidden
●
Provide the following minimum distances for sufficient cooling and mounting:
●
– 50 mm to the bottom side
– 80 mm to the upper side
– 85 mm to the front side
Provide cables with strain relief
●
Attach freely moving cables (e.g. by routing them in a cable channel)
●
Keep as much distance as possible to noise sources when installing the UPS
●
10.3 Mounting
Use drilling holes to mount the UPS in front upright mounting. Use M4 screws.
Mounting, demounting and electric installation
Description
COM interface – Receive Data (Rx)
COM interface – Transmit Data (Tx)
COM interface Ground
Width
55 mm
Height
214 mm
R911384727_Edition 03 Bosch Rexroth AG
15/31
Depth (without plugs)
86.6 mm