Ambient Conditions; Standards; Used Standards - Bosch Rexroth IndraControl VAU 01.1U Project Planning Manual

Vau 01.1u ups with usb interface
Hide thumbs Also See for Rexroth IndraControl VAU 01.1U:
Table of Contents

Advertisement

22/63
Bosch Rexroth AG
Technical Data
4.3

Ambient Conditions

4.4

Standards

4.4.1

Used Standards

In operation
Ambient
tempera‐
+5 °C to +45 °C
ture
Maximum tempera‐
Temporal tempera‐
ture gradient
ture changes up to
3 ℃ per minute
Relative humidity
Climatic class 3K3
according to
EN 60721, conden‐
sation not permissi‐
ble.
Max. 80 % humidity
at 25 °C
Air pressure
Up
to
above
acc. to EN 61131-2
Mechanical
Maximum vibration
strength
Frequency
10 Hz to 150 Hz
Excursion:
mm at 10 Hz to 57
Hz
Acceleration: 1 g at
57 Hz to 150 Hz
Test
each axis: 10 fre‐
quency cycles
Frequency
rate:
1 octave/min
According
60068-2-6, test Fc
Degree of pollution
2
Fig.4-4:
Ambient Conditions
The system components of the VAU 01.1U comply with the following stand‐
ards:
Standard
Meaning
EN 60 61000-6-4
Generic standard, emitted interference (industrial environ‐
ment)
EN 60 61000-6-2
Generic standard, noise immunity (industrial environment)
DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
Transport
-20 ℃ to +60 ℃
Temporal
tempera‐
ture changes up to 3
℃ per minute
Climatic class 3K3
according to
EN 60721, conden‐
sation not permissi‐
ble.
Max. 80 % humidity
at 25 °C
3000
m
Up to 3000 m above
sea
level
sea level acc. to EN
61131-2
Maximum shock:
range:
15 g according to EN
60 068-2-27, no dis‐
turbance of the func‐
0.075
tion
duration
for
sweep
to
EN
2
Storage
-20 ℃ to +60 ℃
Temporal temper‐
ature changes up
to 3 ℃ per minute
Climatic
class
3K3 according to
EN 60721, con‐
densation not per‐
missible.
Max. 80 % humid‐
ity at 25 °C
Up to 3000 m
above sea level
acc.
to
EN
61131-2
Maximum shock:
15 g according to
EN 60 068-2-27,
no disturbance of
the function
2

Advertisement