Equipotential Bonding - Siemens SINAMICS S120 Equipment Manual

Chassis liquid cooled power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

8.1.5

Equipotential bonding

All components in the cooling system (SINAMICS units, heat exchanger, piping system,
pump, pressure compensator, etc.) must be connected to an equipotential bonding system.
A copper bar or stranded copper with the appropriate conductor cross-sections must be used
for this purpose to eliminate electrochemical processes.
If the installation comprises several control cabinets, these must be bolted together in a
solid, conductive connection (e.g. bolt cabinet cross-beams together directly at several
points to make conductive connection). This eliminates potential differences and thus the risk
of electrochemical corrosion. A PE bar must be installed in every cabinet (including the
recooling system) and the individual bars then interconnected.
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
Cooling circuit and coolant properties
8.1 Cooling circuits
239