Current Derating As A Function Of The Pulse Frequency - Siemens SINAMICS S120 Equipment Manual

Chassis liquid cooled power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules
5.6 Technical specifications
5.6.2.4

Current derating as a function of the pulse frequency

When the pulse frequency is increased, the derating factor of the output current must be
taken into account. This derating factor must be applied to the currents specified beforehand
in the technical data.
Table 5- 15
Table 5- 16
Note
For pulse frequencies in the range between the specified fixed values, the relevant derating
factors can be determined by linear interpolation.
168
Derating factor of the output current as a function of the pulse frequency for devices with
a rated pulse frequency of 2 kHz
Order no.
Unit rating
6SL3325-...
[kW]
1TE32-1AAx
110
1TE32-6AAx
132
1TE33-1AAx
160
1TE35-0AAx
250
Derating factor of the output current as a function of the pulse frequency for devices with
a rated pulse frequency of 1.25 kHz
Order no.
Unit rating
6SL3325-...
[kW]
1TE36-1AAx
315
1TE38-4AAx
450
1TE41-0AAx
560
1TE41-4AAx
800
1TG31-0AAx
90
1TG31-5AAx
132
1TG32-2AAx
200
1TG33-3AAx
315
1TG35-8AAx
560
1TG38-1AAx
800
1TG41-0AAx
1000
1TG41-3AAx
1200
Output current for a
pulse frequency of 2 kHz [A]
Supply voltage 510 – 750 V DC
210
260
310
490
Output current for a
pulse frequency of 1.25 kHz [A]
Supply voltage 510 – 750 V DC
605
840
985
1405
Supply voltage 675 – 1080 V DC
100
150
215
330
575
810
1025
1270
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
Derating factor for a
pulse frequency of 4 kHz
82 %
83 %
88 %
78 %
Derating factor for a
pulse frequency of 2.5 kHz
72 %
79 %
87 %
95 %
88 %
84 %
87 %
82 %
85 %
95 %
86 %
79 %
Chassis Liquid Cooled Power Units