Electrical Connection - Siemens SINAMICS S120 Equipment Manual

Chassis liquid cooled power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.2.6

Electrical connection

Operating a Basic Line Module from a non-grounded network (IT system)
When the device is operated from a non-grounded system/IT system, the connection bracket
for the interference-suppression capacitor must be removed.
To do so, loosen the two screws ("1" in the figure below) and pull the connection bracket
towards you out of the device.
Figure 4-8
Failing to remove the connection bracket for the noise suppression capacitor on a non-
grounded system/IT system can cause significant damage to the unit.
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
Removing the connection bracket for the interference-suppression capacitor
WARNING
Line Modules
4.2 Basic Line Modules
99