Parameterizing The Simple Brake Control - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
5.10 Configuring brake control
Commissioning the brake control
Simple brake control is activated automatically (p1215 = 1) when the Motor Module has an
internal brake control and a connected brake has been found. If no internal brake control is
available, the control can be activated via parameter (p1215 = 3).
Danger as a result of a damaged holding brake caused by incorrect parameter assignment
If the drive moves against the closed holding brake, this can destroy the holding brake and as
a consequence result in death or severe injury.
• If a holding brake is being used, do not set the parameter assignment p1215 = 0.
• Set all the relevant parameters correctly.
Note
It is only permissible to activate brake control monitoring for booksize power units and blocksize
power units with Safe Brake Relay (p1278 = 0).
5.10.1.1

Parameterizing the simple brake control

Overview
The following options are available to you for setting the type of brake control:
• Motor holding brake like sequence control
• Motor holding brake always open
• Motor holding brake like sequence control, connection via BICO
Danger as a result of a damaged holding brake caused by incorrect parameter assignment
If the drive moves against the closed holding brake, this can destroy the holding brake and
cause death or serious injury.
• If a holding brake is being used, do not set the parameter assignment p1215 = 0.
• Set all the relevant parameters correctly.
264
WARNING
WARNING
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2