Commissioning
5.9 Commissioning a drive
Assume master control
To activate the control panel, proceed as follows:
1. Click the "Activate" button at "Master control".
The "Activate master control" message window opens.
2. Carefully read the warning note and check the value of the monitoring time.
The monitoring time specifies the time during which the connection from the PG/PC to the
drive is cyclically monitored. The minimum value is 1000 ms.
3. Click "OK" to confirm the monitoring time.
The message window closes.
The control panel is active.
Activating the infeed unit
Note
Not for CU310-2 PN
In a CU310-2 PN with Power Module, no infeed unit is used in the configuration. In this case, the
switch-on/switch-off icons for the infeed unit in the "One Button Tuning" screen form are not
available.
If your drive is equipped with an infeed unit, then this must be switched on. If the infeed unit is
not switched on, then the controller cannot be optimized.
Procedure
Click the "1" icon at "Infeed" to switch on the infeed.
254
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2