Advertisement

Commissioning
5.4 Establishing an online connection to the drive
Result:
• An online connection is possible if the firmware versions are identical.
OR
• If the firmware versions are not identical (see the diagram example above), then the versions
must be aligned in order to be able to establish an online connection. We recommend that
you upgrade the respective older version.
Remedy:
• Update the firmware of your drive device (see Chapter "Updating the firmware (Page 89)").
OR
• In Startdrive, create a new Startdrive project for your drive device, and there, set a more
recent firmware version for the Control Unit (see Chapter "Inserting the Control Unit
(Page 103)"). If you are using an older Startdrive version, it may be necessary to first install
a current Startdrive version.
5.4.2

Online connection via standard service interface X127

Overview
The interface X127 with a default IP address is available for commissioning your drive.
Requirements
New project
• A SINAMICS S120 Control Unit has been inserted in the device configuration.
• You have connected your PG/PC with the drive via the X127 service interface.
Note
You can go directly online as the service interface X127 has already been assigned an IP
address.
Existing project
• If you are using an existing project and devices have already been created, in the project,
check the IP address of the interface in the inspector window at "Properties > General >
Ethernet addresses" and the IP address assigned to the device. The addresses and subnet
masks must be identical.
156
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2