Technical information

8.4 Mechanical ambient conditions

8.4
Mechanical ambient conditions
8.4.1

Storage conditions

The following information is valid for a device that is transported and stored in its original
packaging.
The device was tested according to IEC 60721-3-2 Class 2M4 with the following additions
and restrictions:
Type of condition
Free fall
Vibration according to IEC 60068-2-6
Shock according to IEC 60068-2-27
8.4.2

Operating conditions

The following information applies to a device installed according to the specifications in these
operating instructions.
The device was tested based on IEC 60721-3-3 Class 3M3 with the following additions and
restrictions:
Type of condition
Vibration according to IEC 60068-2-6
Shock according to IEC 60068-2-27
Shock pulses within the specified range can be transferred to the display but do not impact
the functionality of the device.
146
Permitted range
≤ 0.3 m
5 .. 8.4 Hz, deflection 3.5 mm
8.4 ... 500 Hz, acceleration 1 g
250 m/s
, 6 ms, 1000 shocks
2
Permitted range
5 ... 8.4 Hz, deflection 3.5 mm
8.4 ... 200 Hz, acceleration 1 g
150 m/s
, 11 ms, 3 shocks
2
Operating Instructions, 03/2020, A5E46641217-AA