6.17 Encoder diagnostics

Reset the energy display
Set p0040 = 1, to reset the value of parameter r0041 to 0. Parameter p0040 is then
automatically set back to 0.
6.17
Encoder diagnostics
6.17.1
Datalogger
A datalogger is available to support troubleshooting; this datalogger can localize errors in the
encoder evaluation.
Commissioning
Set parameter p0437.0 = 1 to activate this function.
The datalogger is automatically active as soon as the current controller time is slower than
125 μs.
Principle of operation
The datalogger reads out several internal signals of the encoder evaluation, which serve as
basis for the actual value generation. A change in the fault state serves as trigger for the
recording. Data is recorded a short time before the fault state as well as afterwards.
The diagnostics data is saved on the memory card in the following directories:
/USER/SINAMICS/DATA/SMTRC00.BIN
...
/USER/SINAMICS/DATA/SMTRC07.BIN
/USER/SINAMICS/DATA/SMTRCIDX.TXT
The following information is contained in the index file (SMTRCIDX.TXT):
● Displaying the last written BIN file
● Number of still possible write operations (from 10000 downwards).
Note
BIN files can only be evaluated by Siemens.
Alarm A3x930
off the system during this time.
1)
274
is output while diagnostics data is being actively recorded. Do not switch
1)
x = encoder number (x = 1, 2 or 3)
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2