Operation
1
Initial situation
3
➭
Switch the right-hand three-position disconnector to CLOSED
position (insert the operating lever for the DISCONNECTING function
and turn 180° clockwise).
5
➭
Push the interrogation lever downwards again.
172/214
Earthing the busbar section in the right-hand panel
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
➭
Push the right-hand control gate to the left.
4
➭
Remove the operating lever for the DISCONNECTING function.
The interrogation lever and the right-hand control gate return to their
initial position.
6
➭
Push the left-hand control gate to the right.