861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
Connecting the feeder to the busbar
1
Initial situation
3
Push the control gate to the left.
5
Remove the operating lever for the
DISCONNECTING function.
The interrogation lever and the control gate return to
their initial position.
2
Push the interrogation lever downwards.
4
Switch the three-position disconnector to
CLOSED position (insert the operating lever for
the DISCONNECTING function and turn 180°
clockwise).
6
Close the circuit-breaker.
Operation
159/214