Operation
1
Initial situation
3
➭
Push the left-hand control gate to the left.
5
➭
Remove the operating lever for the DISCONNECTING function.
The interrogation lever and the left-hand control gate return to their initial
position.
164/214
37.2
Switching operations in the bus sectionalizer panel
Coupling busbar sections
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
➭
Push the interrogation lever downwards.
4
➭
Switch the left-hand three-position disconnector to CLOSED position
(insert the operating lever for the DISCONNECTING function and turn
180° clockwise).
6
➭
Push the right-hand control gate to the left.