6.3

Cable requirements

6.3.1

Power cables

For information on the requirements for power cables, ground cable and
equipotential bonding conductor, see:
• ACS5000 power cable specification
• Power cables engineering guideline
6.3.2

Auxiliary and control cables

NOTICE
Risk of false signals!
• DO NOT lay control cables in parallel to the power supply cables.
• If this cannot be avoided, a minimum distance of 30 cm must be
maintained between control and power supply cables.
• Cross control and power supply cables at an angle of 90°
Note: For information on the requirements for the auxiliary power cable
and the control cables, see "Auxiliary power and control cables guideline"
3BHS799208 E01 REV E