Connecting The Cables; Checking The Cable Insulation - ABB ACS5000 User Manual

Water-cooled
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

6.7.2

Connecting the cables

CAUTION
Risk of flashover!
High voltages will be present in the terminal compartment. High voltages
can cause flashover between conductors with different electric potential,
and between a conductor and earth.
Therefore, route and connect the cables in such a way that the following
minimum clearances are maintained:
• 70 mm between cable lugs of conductors with a different potential
• 70 mm between the cable lug of a conductor and the parts with
earth potential
• 30 mm between cables with a different potential
6.7.2.1

Checking the cable insulation

• Measure the insulation of each cable before connection and verify
that the results are within the specification of the cable
manufacturer.
• Leave the conductors unconnected at both ends until the
commissioning personnel has given permission to connect them.
3BHS799208 E01 REV E
ACS5000 WATER-COOLED USER MANUAL
06 ELECTRICAL INSTALLATION
108/186